General:
- Power supply: 12/24 V- (8 bis 40 V–)
- Intrinsic consumption: max. 22 W (LT: max. 32 W)
- Ambient temperature (operation): -20 to 70 °C (LT: -40 to 70 °C)
- Ambient temperature (storage): -30 to 80 °C
- Ambient humidity: 95 %, non-condensing
Voltage (Voltage (software configurable): ( /∆)
- 100 Vac Rated (Vrated): 69/120 V~
- Max. value (Vmax): 86/150 V~
- and 400 / 600 Vac Rated (Vrated): 400/690 V~
- Max. value (Vmax): 520/897 V~
- Rated surge volt. (Vsurge): 6,0 kV
- Accuracy: Class 0,5
- Measurable alternator windings: 3p-3w, 3p-4w, 3p-4w OD, 1p-2w, 1p-3w
- Setting range primary: 50 to 650.000 V~
- Linear measuring range: 1,25 × Vrated
- Measuring frequency: 50/60 Hz (30 bis 85 Hz)
- High Impedance Input; Resistance per path: 2,5 MΩ
- Max. power consumption per path: < 0,15 W
Current (Isolated, software configurable):
- Rated (Irated): 1A or 5A
- Linear measuring range: Igen = 3.0×Irated
- Imains/ground = 1.5×Irated
- Setting range: 1 to 32,000 A
- Burden: < 0.10 VA
- Rated short-time overcurrent (1 s): [1] 50×Irated, [5] 10×Irated
- Accuracy: Class 0.5
Power:
- Setting range: 0.5 to 99,999.9 kW/kvar
- Accuracy: Class 1.0
Discrete inputs: isolated
- Input range: 12/24 VDC (8 to 40 VDC)
- Input resistance: approx. 20 kOhms
Transistor outputs (P2 only): isolated
- Rated switching voltage: max. 24 VDC
- Maximum switching voltage: 40 VDC
- Maximum switching current: 300 mA DC
- Isolation Test voltage (<1s): 500 VAC
- Isolation voltage (continuously): 100 VAC/DC
Relay outputs: isolated
- Contact material: AgCdO
- Load (GP): 2,00 A~@250 V~/ 2,00 A–@24 V– / 0,36 A–@125 V– / 0,18 A–@250 V–
Analog inputs (isolated): freely scalable
- Type 1: 0 to 1 V / 0 to 2000 Ohms / 0 to 20 mA
- Resolution: 16 Bit
- Maximum permissible voltage against genset Ground: 9 V
- Maximum permissible voltage between genset Ground & PE : 100 V
- Type 2 (P2 only): 0 to 10 V / 0 to 20 mA
- Resolution: 14 Bit
- Maximum permissible voltage against PE (Ground): 100 V
- Maximum differential voltage to other DC Analog Inputs: 15 V
- Type 3 (P2 only): 0 to 250 Ohms / 0 to 2500 Ohms
- Resolution: 14 Bit
- Maximum permissible voltage against PE (Ground): 100 V
- Maximum differential voltage to other DC Analog Inputs: 10 V
- Analog outputs (isolated): freely scalable
- Type 1: ± 10 V / ± 20 mA / PWM
- Basic insulation voltage (continuously, AVRout): 500 VAC
- Reinforced insulation voltage (continuously, AVRout): 300 VAC
- Insulation voltage (continuously, Govout): 100 VAC
- Resolution: 12 Bit
- Output ± 10 V (scalable): internal resistance
- Output ± 20 mA (scalable): maximum load 500 Ohms
- Type 2 (P2 only): 0/4 to 20 mA
- Insulation voltage (continuously): 100 VAC
- Insulation voltage (test; >2 s): 1700 VAC
- Resolution: 12 Bit
- Output: maximum load 500 Ohms
Housing Front panel flush mounting: Plastic housing
- Dimensions WxHxD: 282 × 216 × 96 mm
- Front cutout WxH: 249 [+1.1] × 183 [+1.0] mm
- Connection: screw/plug terminals 2.5 mm²
- Front: insulating surface
- Sealing :
- Front: IP66 (with screw fastening)
- Front: IP54 (with clamp fastening)
- Back: IP20
- Weight: approx. 1,890 g (P1) / 2.560 g (P2)
Housing Back panel mounting: Powder Coated Sheet metal housing
- Dimensions B x H x T
- P1: : 250 × 228 × 50 mm
- P2: : 250 × 228 × 84 mm
- Connection: screw/plug terminals 2,5 mm²
- Protection system: IP20
- Weight : approx. 1.630 g (P1) / ca. 2480 g (P2)
Disturbance test
- (CE): tested according to applicable IEC standards
Listings:
- CE, UL, EAC, VDE, BDEW. CSA
Marine:
- LR (Type Approval), ABS (Type Approval)
* 3 phase 3 wire - ∆ constellations are limited to 600 VAC system